IBC CODE - WIRE GLASS


For a PDF formatted for 8-1/2 x 11 click here

Illustration of the IBC Change Affecting Use of Wired Glass in Impact/Safety Applications

Outlined below is the old (IBC 2000) and new (IBC 2003) wording regarding Safety Glazing. The areas relevant to wired glass are underlined.

The IBC 2000 edition reads…

IBC 2000…OLD
SECTION 2406
SAFETY GLAZING

2406.1 Human impact loads. Individual glazed area, including glass mirrors, in hazardous locations as defined in Section 2406.2 shall pass the test requirements of CPSC 16 CFR 1201, listed in Chapter 35. Glazing shall comply with the CPSC16 CFR. Part 1201 criteria for Category I or Category II as indicated in Table 2406.1.

Exceptions:
1. Polished wire glass installed in fire doors, fire windows and view panels in fire-resistant walls shall comply with
    ANSI Z971.1 listed in Chapter 35.
2. Plastic glazing shall meet the weathering requirements of ANSI Z97. listed in Chapter 35.
3. Glass-block walls shall comply with Section 2101.2.4.
4. Louvered windows and jalousies shall comply with Section 2403.5.

TABLE 2406.1
MINIMUM CATEGORY CLASSIFICATION OF GLAZING

EXPOSED
SURFACE
AREA OF
ONE SIDE
OF ONE
LITE
GLAZING IN
STORM OR
COMBINATION
DOORS

GLAZING
IN DOORS
GLAZED
PANELS
REGULATED
BY ITEM 7
OF 2406.2

GLAZED
PANELS
REGULATED
BY ITEM 6
OF SECTION
2406.2

DOORS AND
ENCLOSURES
REGULATED
BY ITEM 5 OF
SECTION
2406.2
SLIDING
GLASS
DOORS
PATIO
TYPE

IBC 2003…CURRENT
SECTION 2406
SAFETY GLAZING

2406.1 Human impact loads. Individual glazed area, including glass mirrors, in hazardous locations as defined
in Section 2406.3 shall comply with Sections 2406.1.1 through 2406.1.5.

   2401.6.1.1 CPSC 16 CFR 1201. Except as provided in Sections 2406.1.2 through 2406.1.5, all glazing shall pass    the test requirements of CPSC 16 CFR 1201, listed in Chapter 35. Glazing shall comply with the CPSC 16 CFR,
   Part 1201 criteria, for Category I or II as Indicated in Table 2406.1.

   2406.1.2 Wired Glass. In other than Group E, wired glass installed in fire doors, fire windows and view panels in    fire-resistant walls shall be permitted to comply with ANSI Z97.1.

   2406.1.3 Plastic glazing. Plastic glazing shall meet the weathering requirements of ANSI Z97.1.

   2406.1.4 Glass block. Glass block walls shall comply with Section 2101.2.5.

   2406.1.5 Louvered windows & jalousies. Louvered windows and jalousies shall comply with Section 2403.5.

TABLE 2406.1
MINIMUM CATEGORY CLASSIFICATION OF GLAZING

EXPOSED
SURFACE
AREA OF
ONE SIDE
OF ONE
LITE
GLAZING IN
STORM OR
COMBINATION
DOORS

GLAZING
IN DOORS
GLAZED
PANELS
REGULATED
BY ITEM 7
OF 2406.3

GLAZED
PANELS
REGULATED
BY ITEM 6
OF SECTION
2406.3

DOORS AND
ENCLOSURES
REGULATED
BY ITEM 5 OF
SECTION
2406.3
SLIDING
GLASS
DOORS
PATIO
TYPE

So, what is Group E? It is defined in IBC 2003 below, as…

SECTION 305
EDUCATIONAL GROUP E

IBC 2006…NEW
SECTION 2406
SAFETY GLAZING

ICC Board of Directors Action on 2003/2004 Code Change Appeals

Section 1405.12.2 Add new to read as shown: (FS138-03/04)

Section R613.2 Add new section to read as shown: (RB205-03/04)


Top of the Page